Standard HazMat Buildings and Lockers

Buildings and Lockers are designed for Flammable Liquid Storage, Chemical Storage, and Hazardous Materials in 55-gallon drums. Drum storage buildings / lockers are available in many standard models to help our customers gain OSHA and EPA compliance of your hazardous chemical storage. We offer a wide variety of optional accessories, including explosion proof heating, explosion proof air conditioning, and fire suppression systems. All models are FM approved and Electrical installed in accordance with the NEC 2008 and 2011 editions and include UL Classified electrical accessories. Electrical Classification available at an additional charge. If your requirements call for a more specialized unit, see our Custom HazMat buildings, or our Military/Maritime Spec buildings. Or you can call us for more specific details and options.
Hazmat Storage Lockers are designed for the storage of 55 gallon drums in quantities of 2, 4, 6, 9 and 12 drums. Built to the same specifications as our larger Hazmat buildings, the lockers are FM approved and are EPA & OSHA compliant. These lockers offer the same protection and security with a smaller footprint, and a more economical option when needed. 2 or 4 Hour Fire Rated wall construction Frequently asked questions about Hazmat Storage Buildings See our featured storage locker, AVAILABLE NOW! READY TO SHIP!
Hazmat Storage Buildings are designed for the storage of 16 or more 55 gallon drums up to 80. All Hazmat Models are FM approved and are EPA & OSHA compliant. Electrical installed in accordance with the NEC 2008 and 2011 editions and include UL Classified electrical accessories. Electrical Classification available at an additional charge. Hurricane resistant wall 2 or 4 Hour Fire Rated wall construction
Hazmat Storage Buildings

FEATURES

Industry Leader in Fire Rated Storage – Hazmat Storage Buildings provide the safest and most complete solution for the storage of hazardous chemicals. Our HazMat Buildings come standard with a 6″ deep secondary containment sump to exceed the EPA spill containment requirements as set forth in 40CFR 264.175. Heavy gauge forklift pockets allow for easy loading and off-loading, as well as portability once it gets to your location. All of our buildings are designed in accordance with OSHA and NFPA Code 30 requirements and all Standard Sizes are Factory Mutual Approved. Factory Mutual Aprroval Code 6049 is the standard set forth to establish construction and performance standards for buildings used to store flammable and combustible liquids.

Our buildings are constructed in accordance with FM 6049, and all standard sizes bear the FM Approval Label.

Fire-Rated Storage Buildings:
are constructed based upon UL Fire Resistance Ratings classification criteria. Standard models are available in 2-hour and 4-hour fire ratings. Wall ratings are either 2 or 4 hour fire rated . Roof ratings are either 1.5 or 3 hour fire rated (Check with your local authority having jurisdiction for correct wall/roof rating needed). In addition, all Fire-Rated Buildings come with hydraulic operated self-closing, fire-rated doors and fire damper protected vents.
Four Hour Fire Rating Requirements:
4 Hour Fire Rated wall construction built with a FM Approved and Intertek Tested 3 hrs Fire Rated Roof, 3 hour fire rated door construction, and multiple layers of ¾” gypsum ultracode wallboard. Air inlet vents with UL Classified and labeled fire damper with louvers. Dampers have a galvanized steel frame, curtain-type galvanized steel blades and a UL Classified 165° F fusible link.
Two Hour Fire Rating Requirements:
2 Hour Fire Rated wall construction built with a FM Approved and Intertek Tested 1.5 hrs Fire Rated Roof, 1.5 hour fire rated door construction, and multiple layers of ¾” gypsum ultracode wallboard. Air inlet vents with UL Classified and labeled fire damper with louvers. Dampers have a galvanized steel frame, curtain-type galvanized steel blades and a UL Classified 165° F fusible link.
Approved Explosion Relief Panels:
We are approved to install explosion relief panels on non rated and Fire Rated buildings
Easy to Ship:
Chemical Storage Lockers are designed to fit in a standard high cube shipping container reducing shipping costs and labor time.